With the iGrow1800 controller, you can set up deadbands. Here is a video to give you a more deeper understanding.


Temperature Deadband - For cooling, it is the number of degrees the temperature needs to drop from the lower boundary of its current stage before it switches to the lower stage. Without Deadbands, equipment tends to cycle frequently & constantly change stages when the temperature approaches the set points. When a large value is used, setpoints may not be maintained. Typical values might be 1 to 2 degrees F. For heating it is the number of degrees the temperature needs to rise above the temperature boundary before it switches to a lower heating stage.

Deadband_1.png

 

RelHum Deadband

This is the RH% the humidity must drop below the dehumidification threshold before exiting the dehumidification state.  It also is the RH% the humidity must rise above the humidification threshold before exiting the humidification threshold.

 Bheat Deadband

This is the number of degrees that the bottom heat temperature must rise above the bottom heat temperature setpoint or threshold before the heat valve switches off.  Typical values might be 1 degree F or less.

Temperature Deadband is in Degrees

Relative Humidity Deadband is in Percentages

Bottom Heat (Mix valves/Micro zones) is in Degrees

C02 Deadband is in PPMs

Note: Make sure your Deadband values do not exceed Stage width or the distance between a lower and higher set point

For example, don’t make your deadband for relative Humidity 10% if Humidify is 40% and Dehum is 47%.

Now to get to the deadband programming screen from home screen hit Enter/Menus -> then go into System Setup -> and then Setup Deadbands.

Deadband_2.png

Once you are in the Deadband programming screen, hit Previous and next to navigate between the options and hit +/- to change values within the highlighted fields.
 
Deadband_4.png

Once your finished setting your deadbands hit the back button 3 times to the home screen to save your changes. 
Here is a view of Deadband Programming with LinkConn 1800 Software which provides a simpler control view.

 iGrow1800_-_Programming_Deadbands.png

    • Related Articles

    • iGrow 1400 - Deadband Programming and Understanding

      With the iGrow1400 controller you can set up deadbands. Here is a video to give you a more deeper understanding. iGrow 1400 Deadband Programming and Understanding Now Deadband, sometimes called “hysteresis” band. For cooling, it is the number of ...
    • iGrow 800 Programming Information

      Please view the following videos in the order that there in, so you can program your controller with confidence, and also have an understanding of what Setpoints are for, Staging of your equipment in Temperature and Humidity Stages, as well as how to ...
    • iGrow 800 - Programming C02

      With the iGrow 800, you can control C02 levels within your Greenhouse Environment You would need your firmware updated to at least 1.0.2.1, and a Digital Integrated Sensor Module Installed on the controller. Here is a video link for the iGrow 800 ...
    • iGrow 1400 Equipment Programming Video

      THIS PRODUCT HAS BEEN DISCONTINUED AND REPLACED BY THE PEARL CONTROL SYSTEM. https://link4controls.com/link4_controllers/ Click the link below for additional information on programming equipment for the iGrow 1400.
    • iGrow 1400 - Trigger Irrigation Programming

      With the iGrow 1400, The Irrigation external trigger option is designed to turn on your irrigation valve(s) from an external switch such as a Momentary wall switch. The external trigger input should already be assigned in the Setup Inputs screens. ...