iGrow 800 Temp Probe Fluctuating issues

iGrow 800 Temp Probe Fluctuating issues

Please take the following steps in troubleshooting your Temperature Probe.
 
·        iGrow 100 Series Sensor Troubleshooting

 
  1. Check connection’s inside junction box (if one exists) for moisture or corrosion
  1. Check the PCB for corrosion, moisture or contamination build up.
  1. Check the line that leads to that box for cuts or any damage which will affect the sensors readings.
  1. Check for wire any interference sources (voltage, motors, inverters, etc….)
  1. Cycle equipment ON and OFF and see if Sensor Reading appears or Stabilizes
  2. Check the power supply P/S and see if dropdown voltage AC to 12VDC is accurate.
o   Since incorrect voltage can discourage the logic within the device.

Try powering iGrow from a different circuit entirely (extension cord across the way or an inverter) and see if the sensor stabilizes
Sensor Reading Jumping Around and not constant.
Do troubleshooting steps first – when it JUMPS that indicates some type of Interference.
·         Try toggling OFF outputs 1 by 1 until all are OFF to see if sensors STABLIZES.
·         NEXT, toggle them ON to see if a power change creates fluctuation. 
·         Try powering iGrow from a different circuit entirely (extension cord across the way or an inverter)
·         If controllers are Daisy Chained to one 12V source, try powering 12V independently. With an additional P/S
·         How longs the Sensor wire  (150ft max)
·         Who spliced the wire?
·         Is the shield grounded?
IF ALL ELSE FAILS THERE ARE 3 OPTIONS AVAILABLE
-          Use a shielded cable
-          Install a filter PCB at the iGrow
-          Use a digital temp/hum sensor
    • Related Articles

    • iGrow 1400 - Analog Temp Probe Troubleshooting

      THIS PRODUCT HAS BEEN DISCONTINUED AND REPLACED BY THE PEARL CONTROL SYSTEM. https://link4controls.com/link4_controllers/ If your Analog Probe is displaying wrong readings, spiking up and down or not reading at all its time to take steps in ...
    • ***** iGrow Sensor Info, Issues and Troubleshooting

      iGrow 100 series Sensor Issues Outdoor/Indoor Temp/Hum Sensor Troubleshooting Temperature sensor not registering. Check sensor connection wires on the controller to make sure there tight and securely fastened. Check connections inside junction box ...
    • iGrow 800 - Temperature Probe Installation

      Please view the following in installing Analog Temperature Probes on the iGrow400/800 Controller. Once you have landed your Temp Probe you would have to go into the Controllers Programming to Map the Sensor to the controller
    • iGrow 800 Sensor Jumping issues

      Please take the following steps in troubleshooting your Temperature Probe. · iGrow 100 Series Sensor Troubleshooting - Check connection’s inside junction box (if one exists) for moisture or corrosion - Check the PCB for corrosion, moisture or ...
    • iGrow 100 Analog Probe Wiring & Progamming

      Please download the attached 100 Series Analog Probe Installation & Programming guide.