iGrow 800 Alarm & Face Separation Issues

iGrow 800 Alarm & Face Separation Issues

Please take the following steps to format file system
 
1st SAVE EXISTING CONFIGURATION SETTINGS (set points/equipment settings/stages).
To save your configuration you would do the following:
Insert USB stick into controller
Press OK-> SystemSetup->SaveRestore->SaveRestoreConfig->SaveConfig (button 1)
A window will pop up with options - you want to save to USB-> then enter file name and press OK
NOTE: follow same steps when restoring configuration, but instead of saving you would be restoring (button 2)


2nd FORMAT FILE SYSTEM/CLEAR HISTORY
OK-> System Setup-> Advance-> clear all data (button 3) -> 1st Clear History (button 1) 2nd format file system (button 2) then a window will pop up saying "this will remove all web server files"   choose - YES
3rd before re-installing configuration program a High Alarm Output
Map your InTemp Sensor so that is is viewable and is displaying a value
Then do the same process as before, manipulating the alarm to see if the output engages.
If it works, load your configuration, if it does not, call support.

4th INSTALL YOUR SAVED CONFIGURATION FILE